ASi Master Communication Processor
May 16, 2008 9:17 pm, by zaki
Subject : Communications
from the FCG dept.
Text :
Hi to all,

Does anybody can help me about ASi master communication Processor. I need to add 1 Asi master (CP-342-2) module for the main rack. My existing Master using extended operation configuration. Please help me to do it again for the next additional master (CP 342-2) by using extended operation. Anybody from Siemens people can contribute even small ideas. It would be a great help.

Thank you very much in advance,

rey
Reply


  • Re: ASi Master Communication Processor
    May 17, 2008 12:33 pm, by MHAMZA
    Dear Zaki,
    Open a copy of your existing Step-7 program in Simatic Manager and add another AS-i CP from hardware catalog save and compile.
    Then open your Step-7 progam OB and FB where the first CS-i CP342-2 has been used with extended functions and copy them to new FB. Change the addresses according to the new assignment of the second AS-i CP342-2 and modify the logic according to your requirement.
    Reply

  • Re: ASi Master Communication Processor
    May 18, 2008 5:12 pm, by zaki
    Hi Namzha,

    Is there any addressing for another Asi Master like for diagnosing the module?since ther are 2 master now connected?By the way ID Module for Asi is 28 am I correct?

    It means, that my existing DB31 for Asi read write block will also create another DB like DB32 for another master?

    It says hear standard DB for Asi is DB31?and DB 58 for alarm.

    It is posible to have more than 1 CP_DB if exist one more than 1 CP342_2?

    OHH quite long ,,,
    I am very much appreciated with ur first reply,,

    zaki
    Reply

  • Re: ASi Master Communication Processor
    May 20, 2008 12:45 am, by MHAMZA
    Dear Zaki,

    The diagnostic address for the second AS-i CP342-2 can be found in the hardware configuration of your Step-7 program. You may send me zip (archive) Step-7 software so I am able to answer your questions. The DB31 for the first CP-342-2 is most probably an instance DB for a FB handling the As-i CP342-2. When you call this FB in your OB1 it will ask you to assign a DB number for its instance Datablock, you may put DB32 if there is no DB32 in your existing software.
    My email is muhammad. hamza. kmh @ gmail. com
    Reply

  • The man who sets out to carry a cat by its tail learns something that will always be useful and which never will grow dim or doubtful. - Mark Twain
    Your use of this site is subject to the terms and conditions set forth under Legal Notices and the Privacy Policy. Please read those terms and conditions carefully. Subject to the rights expressly reserved to others under Legal Notices, the content of this site and the compilation thereof is ©1999-2006 Control Technology Corporation. Powered by Python, Zope, and Squishdot, inspiration by Slashdot. (Vers.ZSQ1.0) -va-